HLS-1D Hydrostatic FRP Double-wall Tank Leak Detection Sensor

FRP double-wall tanks are usually filled with monitoring fluid in the interstice. Normally, the monitoring fluid level should keep in the middle of the reservoir which is on the top of the tank. OKet® provides HLS-1D dual-point hydrostatic sensor which can accurately detect fluid-level changes in reservoir in high or low level change. If the brine solution seeps into the tank, lowering the level in the reservoir, the sensor triggers a low-level alarm. If an outer wall leak occurs and groundwater seeps into the tank, a high alarm is activated.


Functions:


  • Distinguishes inner or outer wall  leaks via liquid level

  • Inner leak: Low-level alarm

  • Outer leak: High-level (high groundwater) or low-level (low groundwater) alarm



Parameters:


  • Operating temperature range: -20℃~60℃ (saline); 0℃~60℃ (no freezing water)

  • Size: Length 385 mm; Diameter 50 mm

  • Alarm point: 50 mm (low level); 295 mm (high level) (customizable)

  • Enclosure protection class: IP68

  • Sensor accuracy: ≤2 mm


RELATED PRODUCTS